You are here: home  > Variable Frequency Resonant (VF) Test System-Solution Brief

Variable Frequency Resonant (VF) Test System-Solution Brief 

Price: 1000.0 USD 
Payment Terms: T/T,L/C 
Place of Origin: Hubei, China (Mainland) 
inquire skype
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: SXBP-10000kVA/600kV
Production Capacity: 100 per year
Delivery Date: 15-30 working days
Means of Transport: Ocean,Land,Air
Packing: Plywood case
Brand Name: Sansionpower

The system is specially designed for AC withstand voltage test

Test Object and Requirement

The system is specially designed for AC withstand voltage test for below items, with below specifications and requirements.

Test Object

Specifications

Test Frequency

Test Voltage

Test Time

Power cable

170kV/2000mm2/10km

Capacitance ≤2μF

30-300Hz

150kV

15 mins

Power cable

400kV/2000mm2/5km

Capacitance ≤0.6μF


30-300Hz

220kV

15 mins

GIS

400kV and below  Capacitance ≤0.02μF

30-300Hz

Max. 750kV


Capacity Determination of the equipment:

4pcs Reactors will be designed, each reactor is 2500 kVA/150kV. Capacity amount is 10000kVA.

Determination:

1)    When to do AC withstand voltage testing on 170kV 2000mm2 10kM power cable.

Using 4pcs reactors in paralleled.

Output 150kV/66.6A, testing current is calculated as below:

I=U×103×ω×C×10-6=66A (U:150kV,C:2uF,ω=2πf (f=35Hz))

2)    When to do AC withstand voltage testing on 400kV 2000mm2 5kM power cable,

Using 2pcs reactors in series and then these two groups in paralleled.

Output 300kV/33.3A, testing current is calculated as below:

I=U×103×ω×C×10-6=29A (U:220kV,C:0.6uF,ω=2πf (f=35Hz))

3)    When to do AC withstand voltage testing on 400kV and below voltage degree GIS and etc. equipment, the capacitance is 0.02 uF,

Using 4pcs reactors in series, output 600kVA/16.6A, resonant frequency and testing current is calculated as below:

I=U×103×ω×C×10-6=3.3A (U:512kV,C:0.02uF,ω=2πf (f=50Hz))


                REACTORS


TEST OBJECT

Testing Voltage (kV)

REACTOR    2500KVA/150kV  

OUTPUT VOLTAGE OF EXCITING TRANSFORMER

170KV Power Cable

150

4 pcs reactors in paralleled

7.5KV

400KV Power Cable

220

2 pcs reactors in series, then two groups in parralled

15kV

400kV GIS

512

4 pcs in series

30kV


Ms. Ying
skype Ms. Ying

Tel: 86-27-83385600
Contact to this supplier

Didn't find what you're looking for? Post Buying Lead or contact HiSupplier Customer Service Center  for help!

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Sansion Power Electric Co., Ltd. [China (Mainland)]


Business Type:Manufacturer, Trading Company
City: Wuhan
Province/State: Hubei
Country/Region: China (Mainland)

skype:   skype

You May Like:

Product (30)